      General specification
      General Standards 
      The product is designed and produced to comply with BS EN60947-4-3 (Low
      voltage switch gear and control gear). Other applicable standards are cited
      where appropriate.
      Installation Categories 
      General installation category details for the driver and power units are
      summarised in the table below.
      Installation Rated impulse Rated 
      Category withstand insulation
      voltage (Uimp) voltage
      Communications II 0.5kV 50V
      Standard/Optional I/O II 0.5kV 50V
      Driver module power II 2.5kV 230V
      Relays III 4kV 230V
      Power Modules (up to 600V) III 6kV 600V
      Power Modules (690V) II 6kV 690V
      Auxiliary (fan) supply II 2.5kV 230V
      Power (at 40°C) 
      Caution
      Although the driver module supply voltage range is 85 to 265V ac, the
      fans (if any) fitted to the power (thyristor) modules are specified for use
      at one of 115V ac or 230V ac as specified at time of order. Before
      plugging the fan harness into the driver module, ensure that the utility
      supply voltage is suitable for the fan(s). Otherwise, fan life may be
      shortened or the cooling effect may not be sufficient, either case
      presenting a possible hazard to the equipment or to the operator.
      Driver module
      Voltage range:  100 to 240V ac (+10% - 15%)
      Frequency range:  47 to 63Hz
      Power requirement:  60W + Power Module fans 
      (15W each for 400A/500A/630A power 
      modules; 
      10W each for 160A/250A modules)
      Power module
      Number of modules:  Up to four identical units per driver unit
      Voltage range:  100 to 600V ac (+10% - 15%) or 
      100 to 690V ac (+10% - 15%) 
      as specified at time of order
      Frequency range:  47 to 63Hz
      Nominal current:  16 to 630A  depending on power module
      Power dissipation:  1.3W per Amp per phase
      Cooling
      Up to and including 100A:  Natural convection
      Above 100A:  Fan cooling. Fans are connected in parallel 
      to driver module connector
      Fan supply voltage:  115 or 230V ac, as specified at time of order
      (see ‘Caution’ above)
      Protection Thyristor drive:  RC circuits and high-speed fuses (Type 1)
      Pollution degree: Pollution degree 2 (EN60947-1)
      Rated short circuit 
      conditional current: 92kA
      Utilisation categories AC51: non inductive or slightly inductive loads, 
      resistance furnaces
      AC56a: switching of transformers
      Duty cycle: Uninterrupted duty/continuous operation
      Form designation: Form 4
      Short circuit protection
      co-ordination type: Type1
      Load types:  Single or multiphase control of resistive 
      loads (low/high temperature coefficient and
      non-aging/aging types) and transformer 
      primaries. Load voltage/current feedback 
      either internal (standard) or external 
      (option for use with transformer 
      secondaries for example)
      Physical 
      Dimensions and fixing centres  See Fixing Details
      Weight kg (lbs): 
      (including 2kg for driver module)
      Current 1 phase 2 phases 3 phases 4 phases
      50A 6.5 (14.3) 11.0 (24.3) 15.5 (34.2) 20.0 (44.1)
      100A 6.5 (14.3) 11.0 (24.3) 15.5 (34.2) 20.0 (44.1)
      160A 6.9 (15.2) 11.8 (26.0) 16.7 (36.8) 21.6 (47.6)
      250A 7.8 (17.2) 13.6 (30.0) 19.4 (42.8) 25.2 (55.6)
      400A 11.8 (26.0) 21.6 (47.6) 31.4 (69.2) 41.2 (90.8)
      500A 14.0 (30.9) 26.0 (57.3) 38.0 (83.8) 50.0 (110.2)
      630A 14.5 (32.0) 27.0 (59.5) 39.5 (87.1) 52.0 (114.6)
      Environment 
      Temperature limits Operating:  0°C to 50°C (derate above 40°C as per 
      accompanying curves)
      Storage:  -25°C to 70°C
      Atmosphere:  Non-explosive, non-corrosive and 
      non-conductive
      Humidity limits:  5% to 95% RH (non-condensing)
      Altitude (maximum):  1000 metres
      Protection: IP10 (EN60529)
      External wiring:  Must comply with IEC 364
      Shock (EN60068-2-29): 10g Pk; 6mS duration; 10 bumps
      Vibration (EN60068-2-6):  67-150Hz at 1g
      EMC 
      Standard:  EN60947-4-3 Emissions class A
      This product has been designed for 
      environment A (Industrial). Use of this  
      product in environment B (domestic, 
      commercial and light industrial) may cause  
      unwanted electromagnetic disturbances in 
      which cases the user may be required to take 
      adequate mitigation measures.
      Immunity criteria: Immunity criterion 1 (criterion 3 for voltage 
      dips and short-time interruptions)
      Operator Interface 
      Display:  4 lines of up to 10 characters each. Display 
      pages can be used to view process variable 
      values and to view and edit the 
      configuration of the unit. (Editing of the 
      configuration is better carried out using 
      configuration software (iTools). In addition 
      to the standard displays, up to four ‘custom’
      pages can be defined which allow bargraph 
      displays, text entry etc.
      Character format:  7 high x 5 wide yellow-green LCD dot matrix 
      array
      Push buttons: 4 push buttons provide page and item entry
      and scroll facilities
      LED indicators (beacons):  3 indicators (PWR LOC and ALM) are 
      supplied to indicate that power is applied, 
      that Local Control  is selected and that 
      there is one or more active alarm 
      respectively
      Standard Inputs/Outputs (SK1) 
      All figures are with respect to driver module 0V, unless otherwise stated.
      Number of inputs/outputs
      No of analogue inputs: 2
      No of analogue outputs: 1
      No of digital inputs/outputs: 2 (each configurable as an input or an 
      output)
      10V (Potentiometer) supply: 1
      Update rate:  Twice the mains frequency applied to power
      module 1. Defaults to 83.2Hz (12mS) if no 
      power applied to power module1 or if the 
      frequency lies outside the range 47 to 63Hz)
      Termination:  Removable 10-way connector. (5.08 mm. 
      pitch)
      Analogue Inputs 
      Performance: See Tables 1 and 2
      Input types: Each input is configurable as one of: 0 to 
      10V, 1 to 5V, 2 to 10V, 0 to 5V, 0 to 20mA,    
      4 to 20 mA
      Absolute maxima + terminal: ±16V or ±40mA
      - terminal: ±1.5V or ±300mA
      500
      400
      300
      200
      100
      0

      100 Amp unit
      50 Amp unit
      Temperature °C
      Maximum current (A)
      600
      160 Amp unit
      250 Amp unit
      400 Amp unit
      500 Amp unit
      630 Amp unit

      Analogue input: Voltage input performance
      Parameter Typical Max/Min
      Total voltage working input span (Note 1) -0.25V to +12.5V
      Resolution (noise free) (Note 2) 13 bits
      Calibration error (Notes 3 and 4) <0.25% <0.5%
      Linearity error (Note 3) ±0.1%
      Ambient temperature error (Note 3) <0.01%/°C
      Input resistance (+‘ve terminal to 0V) >140kΩ
      Input resistance (-‘ve terminal to 0V) 150Ω
      Allowable voltage (-‘ve terminal to 0V) ±1V
      Series mode rejection of mains interference 46dB >30dB
      Common mode dc rejection 46dB >40dB
      Hardware response time 5ms  
      Note 1: w.r.t. to the relevant -‘ve input
      Note 2: w.r.t. total working span
      Note 3: % of effective range (0 to 5V, 0 to 10V)
      Note 4: After warm up. Ambient = 25°C
      Table 1  Analogue input specification table (voltage inputs)
      Analogue input: Current input performance
      Parameter Typical Max/Min
      Total current working input span -1mA to +25mA
      Resolution (noise free) (Note 1) 12 bits
      Calibration error (Notes 2 and 3) <0.25% <0.5%
      Linearity error (Note 2) ±0.1%
      Ambient temperature error (Note 2) <0.01%/°C
      Input resistance (+‘ve to -’ve terminal) 235Ω
      Input resistance (-‘ve terminal to 0V) 150Ω
      Allowable voltage (-‘ve terminal to 0V) <±1V
      Series mode rejection of mains interference 46dB >30dB
      Common mode dc rejection 46dB >40dB
      Hardware response time 5ms
      Note 1: w.r.t. total working span
      Note 2: % of effective range (0 to 20mA)
      Note 3:  After warm up. Ambient =25°C
      Table 2  Analogue input specification table (current inputs)
      Analogue outputs 
      Performance: See Tables 3 and 4
      Output types: Each output is configurable as one of 0 to 
      10V, 1 to 5V, 2 to 10V, 0 to 5V, 0 to 20mA,  
      4 to 20 mA
      Absolute maxima + terminal: (-0.7V or -300mA) or (+16V or +40mA)
      0V terminal: ±2A
      Analogue output: Voltage output performance
      Parameter Typical Max/Min
      Total voltage working span -0.5V to +12.5V
      (within ±20mA (typ.) current span)
      Short circuit current <24mA
      Resolution (noise free) (Note 1) 12.5 bits
      Calibration error (Notes 2 and 3) <0.25% <0.5%
      Linearity error (Note 2) <±0.1%
      Ambient temperature error (Note 2) <0.01%°C
      Minimum load resistance >800Ω
      DC output impedance <2Ω
      Hardware response time (10% to 90%) 20ms <25ms
      Note 1: w.r.t. total working span
      Note 2: % of effective range (0 to 5V, 0 to 10V)
      Note 3: After warm up. Ambient = 25°C 
      Table 3  Analogue output specification table (voltage outputs)
      Analogue output: Current output performance
      Parameter Typical Max/Min
      Total current working span -24mA to +24mA
      (within -0.3V to +12.5V voltage span)
      Open circuit voltage <16V
      Resolution (noise free) (Note 1) 12.5 bits
      Calibration error (Notes 2 and 3) <0.25% <0.5%
      Linearity error (Note 2) <±0.1%
      Ambient temperature error (Note 2) <0.01%°C
      Maximum load resistance <550Ω
      DC Output conductance <1μA/V
      Hardware response time (10% to 90%) 20ms <25ms
      Note 1: w.r.t. total working span
      Note 2: % of effective range (0 to 20mA)
      Note 3: After warm up. Ambient = 25°C 
      Table 4  Analogue output specification table (current outputs)
      10V supply (Potentiometer supply)
      Output voltage: 10.0V ± 0.3V @ 5.5mA
      Short circuit o/p current: 15mA max.
      Ambient temperature drift: ± 0.012%/°C (typ); ±0.04%/°C (max.)
      Absolute maxima  Pin 1: (-0.7V or -300mA) or (+16V or +40mA)
      Digital I/O
      Hardware response time: 100μs
      Voltage inputs 
      Active level (high): 4.4V<Vin<30V
      Non-active level (low): -30V<Vin<+2.3V
      Input impedance: 10kΩ
      Contact closure input 
      Source current: 10mA min; 15mA max
      Open contact 
      (non active) resistance:  >500Ω
      Closed contact 
      (active) resistance:  <150Ω
      Current source output 
      Source current: 9mA<Isource<14mA @ 14V
      10mA<Isource<15mA @ 0V
      9mA<Isource<14mA @ -15V
      Open circuit voltage: <14V
      Internal pull-down resistance: 10kΩ (to 0V)
      Absolute maxima + terminal: ±30V or ±25mA
      - terminal: ±2A
      Notes:
      1. Absolute maximum ratings refer to externally applied signals
      2. The 10V potentiometer supply is designed to supply two 5kΩ
      potentiometers connected in parallel with one another.
      3. The maximum current for any 0V terminal is ±2A.
      Relay Specification 
      The relays associated with this 
      product have gold plated contacts 
      applicable to ‘dry circuit’ 
      (low current) use.
      Contact life Resistive loads: 100,000 operations (de-rate with inductive
      loads as per figure)
      High power use  Current: <2A (resistive loads)
      Voltage: <264V RMS
      Low power use  Current: >1mA
      Voltage: >1V
      Contact configuration:  Single pole change-over (One set of 
      Common, Normally Open and Normally 
      Closed contacts)
      Termination Relay 1 (standard): 3-way connector on underside of driver 
      unit 
      Watchdog relay (standard): 3-way connector on underside of driver 
      unit 
      Relays two to four (option): 12-way option module connector
      Absolute max switching capability: <2A at 240V RMS (resistive loads)
      Note: Normally closed and normally open refer to the relay when the coil
      is not energised.
      Optional Input/Output Modules (SK3, SK4, SK5)
      Up to three input/output modules can be fitted, each containing the inputs
      and outputs detailed below. Unless otherwise stated below, the specification
      for the optional I/O (including relays) is as given above for the standard I/O.
      Termination: Removable 12-way (5.08mm pitch) 
      connector per module
      Number of modules: Up to 3
      Number of inputs: 1 analogue input and 2 digital inputs per 
      module
      Number of outputs: 1 analogue output per module
      Number of relays: 1 set of common, normally open and 
      normally closed contacts per module
      10V potentiometer supply 
      output voltage: 10.0V ±0.3V at 5.5mA
      0.3
      0.4
      0.5
      0.6
      0.7
      0.8
      0.9
      1.0
      1 0.8 0.6 0.4 0.2
      Reduction factor
      Inductive life = resistive life x reduction factor

      Mains Network Measurements
      All network measurements are calculated over a full mains cycle, but
      internally updated every half-cycle. For this reason, power control, current
      limits and alarms all run at the mains half-cycle rate. The calculations are
      based on network waveform samples, taken at a rate of 20kHz. 
      Measurements on each network phase are synchronised to its own phase
      and if the line voltage cannot be detected, the measurements will stop for
      that phase. It should be noted that, depending on the network
      configuration, the phase voltage referred to is one of:
      a. the line voltage referenced to neutral in four star,
      b. the line voltage referenced to neutral or another phase for single phase 
      networks or
      c.  the line voltage referenced to the phase applied to the next adjacent 
      power module for three phase star or delta networks.
      The parameters below are directly derived from measurements for each
      phase.
      Accuracy (20 to 25°C)
      Line frequency (F): ±0.1Hz
      Line RMS voltage (Vline): ±0.5% of Nominal Vline
      Load RMS voltage (V): ±0.5% of Nominal V for readings
      >1% of Nominal V
      Thyristor RMS current (IRMS): ±0.5% of Nominal IRMS for current 
      readings >3.3% of Nominal IRMS
      Unspecified for readings <3.3% of 
      Nominal IRMS
      Note:  For external current feedback this 
      specification does not include errors
      associated with external current 
      transformers.
      Load RMS voltage squared (Vsq): ±1% of (Nominal V)2
      Thyristor RMS current squared (Isq): ±1% of (Nominal I)2
      True load power (P): ±1% of (Nominal V) x (Nominal I)
      Frequency resolution:  0.01Hz
      Measurement resolution:  11 bits of Nominal value (noise 
      free)
      Meas. drift with ambient temp: <0.02% of reading /°C
      Further parameters (S, PF, Q, Z, Iavg, IsqBurst, IsqMax, Vavg, Vsq Burst,
      VsqMax and PBurst) are derived from the above, for each network 
      (if relevant). See EPower User Guide Section 6.19.1 (Meas submenu) for
      further details.
      External Current Transformer
      Ratio:  Chosen such that the full scale 
      output from the current transformer
      is 5 Amps
      Communications
      Modbus TCP (Ethernet)  Type: 10baseT (IEEE801)
      Protocol: Modbus TCP
      Connector: RJ45 with indicators 
      (Green = Tx activity; 
      Yellow = Network activity)
      Modbus RTU  Protocol: Modbus RTU slave
      Transmission standard: 3-wire EIA485
      Connector: Twin, parallel-wired RJ45, with 
      indicators (Green = Tx activity; 
      Yellow = Rx activity)
      Isolation (EN60947-4-3): Installation category II, Pollution 
      degree 2
      Terminals to ground: 50V RMS or dc to ground (double 
      isolation)
      DeviceNet: Protocol: DeviceNet
      Connector: 5-way with indicators 
      (Network Status and Module Status) 
      Profibus: Protocol: Profibus DPV1
      Connector: 9-way D type with indicators 
      (Operator Mode and Status)
      EtherNet/IP: Protocol: EtherNet/IP
      Connector: RJ45 with 3 indicators
      CC-Link:  Protocol: CC-Link version 1.1
      Connector: 5-way with indicators